WTDQ DZ47LE-125 C100 Miniature High Break Leakage Circuit Breaker(4P)

Short Description:

The pole number of a small high breaking leakage circuit breaker is 4P, which means it has four power input terminals and one main switch. This type of product is typically used to protect electrical equipment in homes or small business premises from faults such as overload, short circuit, and leakage.

1. Strong safety

2. High reliability

3. Low cost

4. Multifunctionality

5. Reliability and Durability


Product Detail

Product Tags

Short Description

1. Strong safety: With multiple power input ports, multiple electrical devices can be connected simultaneously, thereby improving the safety of the circuit. When one of the appliances malfunctions, the other appliances will not be affected and will continue to operate or be damaged.

2. High reliability: Small high breaking leakage circuit breakers are made of advanced electronic components and high-quality materials, resulting in stable and reliable performance and long service life. Under normal working conditions, the product can quickly respond and cut off fault current, avoiding the occurrence of fire or personal injury accidents caused by leakage.

3. Low cost: Compared with traditional single-phase leakage circuit breakers, products such as small high breaking leakage circuit breakers and four wire leakage circuit breakers are relatively inexpensive and easy to install. This is a good choice for family users with limited budgets.

4. Multifunctionality: In addition to basic leakage protection and overload protection functions, small high breaking leakage circuit breakers can also achieve more functions through additional modules, such as remote monitoring, alarm, etc. This makes the product more suitable for situations that require multiple protective functions.

5. Reliability and Durability: The small high breaking leakage circuit breaker has undergone strict testing and certification, ensuring its reliability and stability. In addition, due to its compact structure and compact size, it is very suitable for installation in limited spaces, such as wall sockets or switch panels.

Product Details

图片4

Technical Parameter

Type

DZ47LE-125 (NC100LE)

Pole

1P+N, 2P

3P, 3P+N, 4P

Rated current (A)

63A,80A,100A,125A

Rated voltage(V)

230V

400V

Rated short circuit breaking capacity Icn(KA)

6KA

Rated residual making/breaking capacity

2000A

Rated residual action current

30mA, 100mA, 300mA

Rated residual non-action current

0.5 x rated residual action current

Over voltage protection grade

280V±5%

 

 

The over-current protection property

Ambient Temperature

Initial Status

Test Current

Expected Result

Expected Result

NOte

40±2oC

Cold position

1.05In(In≤63A)

t≤1h

Non-release

-

Cold position

1.05In (In[63A)

t≤2h

Non-release

-

Carried out immedi-ately after previous test

1.30In(In≤63A)

t < 1h

Release

Current smoothlyrises to specified value within 5s

1.30In (In>63A)

t< 2h

Release

-5~+40oC

Cold position

8.00In

t≤0.2s

Non-release

-

Cold position

12.00In

t < 0.2s

Non-release

-

Dimension

图片5

  • Previous:
  • Next:

  • Related Products